Description
The SE-105/SE-107 is a combination ground-wire monitor and ground-fault relay for resistance-grounded systems. It continuously monitors the integrity of the ground conductor to protect portable equipment from hazardous voltages caused by ground faults. The SE-105/SE-107 is an excellent choice for trailing cables 5 kV and under in underground mining applications. For higher voltages or long-cable applications, see the SE-134C/SE-135.
Features & Benefits
Adjustable pickup (0.5, 2.0, 4.0 A)
Unit can be used on a wide variety of trailing cable applicationsAdjustable time delay (0.1-2.0 s)
Adjustable trip delay for quick protection and system coordinationHarmonic filter
Prevents false operationZener-characteristic termination assembly
Provides reliable ground-check loop verificationFail-safe ground-check circuit
Ensures ground-check circuit remains safe even in the event of equipment failureConformal coating
Additional coating protects circuit boards against harsh environmentSE-105: Selectable UV- or shunt-trip mode
Provides flexibility for different applicationsSE-107: UV-trip mode only
Eliminates chance of unauthorized change to trip circuit
SE-105 SE-107 Datasheet
SE-105 Manual
Specifications
- IEEE Device Numbers: Checking or Interlocking Relay (3GC), Ground Fault (50G/N, 51G/N)
- Input Voltage: See ordering information
- Dimensions: H 150 mm (5.9”); W 109 mm (4.3”); D 100 mm (4.0”)
- Trip Level Settings: 0.5, 2.0, 4.0 A
- Trip Time Settings: 0.1-1.0 s
- Contact Operating Mode: Selectable fail-safe or non-fail-safe (SE-105) Fail-safe only (SE-107)
- Harmonic Filtering: Standard feature
- Reset Button: Local and remote
- Output Contacts: Isolated Form A
- Approvals: CSA certified, UL Listed (E340889), C-Tick (Australian)
- Conformally Coated: Standard feature
- Warranty: 5 years
- Mounting: Surface
Ordering Information
ORDERING NUMBER | CONTROL POWER |
SE-105 | 120 VAC |
SE-105D | 120 VAC/VDC |
SE-105E | 240 VAC |
SE-107 | 120 VAC |
SE-107D | 120 VAC/VDC |
SE-107E | 240 VAC |
ACCESSORIES | REQUIREMENT |
CT200 Series | Required |
1N5339B | Included |
SE-TA6, SE-TA6-SM | Optional |
SE-TA6A Series | Optional |
RK-102, RK-105, RK-105I | Optional |
RK-13 | Optional |
PPI-600V | Optional |
Accessories
CT200 Series Current Transformer
Required CT detects ground-fault current.
1N5339B Termination Device
5 W axial-lead ground-check termination; included with SE-105/SE-107.
SE-TA6 Termination Assembly
Optional termination assembly with convenient terminals and mounting holes
SE-TA6-SM Stud-Mount Termination Assembly
Optional 50 W ground-check termination that is robust and compact for submersible pumps. Wire lead simplifies installation.