The SE-704 is a microprocessor-based ground-fault relay for resistanceand solidly-grounded systems. It offers very sensitive ground-fault detection as low as 10 mA and can be used on systems with significant harmonic content. The SE-704 provides feeder-level protection or individual-load protection. The output contacts can be connected for use in protective tripping circuits or in alarm indication circuits. The analog output can be used with a PLC or a meter.
Features & Benefits
Adjustable pickup (10 mA-5 A)
Adjustable trip setting provides a wide range of low-level protection and system coordinationAdjustable time delay (30 ms-2.0 s)
Adjustable trip delay allows quick protection and system coordinationOutput contacts
Form A and Form B ground-fault output contacts for operation of separate annunciation and trip circuitsAnalog output (0-5 V & 0-1 mA)
Allows for connecting an optional meter (PGA-0500) or control systemCT-Loop monitoring
Alarms when CT is not connectedSelectable contact operating mode
Selectable fail-safe or non-fail-safe operating modes allows connection to shunt or undervoltage breaker coilHarmonic filtering
Eliminates nuisance trippingNon-volatile trip memory
Retains trip state when de-energized to simplify troubleshootingMicroprocessor based
No calibration required saves maintenance costUniversal power supply
Allows operation in application where one side of PT is faulted, provides flexibility for numerous applications
SE-704 Datasheet
SE-704 Manual
TN CT-01 Ground Fault CT Selection Guide
Specifications
- IEEE Device Numbers: Ground fault (50G/N, 51G/N)
- Input Voltage: See ordering information
- Dimensions: H 75 mm (3.0"); W 55 mm (2.2"); D 115 mm (4.5")
- Trip Level Settings: 10 mA-5.0 A
- Trip Time Settings: 30-2000 ms
- Contact Operating Mode: Selectable fail-safe or non-fail-safe
- Harmonic Filtering: Standard feature
- Test Button: Standard feature
- Reset Button: Standard feature
- CT-Loop Monitoring: Standard feature
- Output Contacts: Isolated Form A and Form B
- Approvals: UL Listed (E340889), CSA, CE (European Union) C-Tick (Australian)
- Analog Output: 0-5 V & 0-1 mA
- Conformally coated: Optional
- Warranty: 5 years
- Mounting: DIN, Surface (standard) Panel (with PMA-55 or PMA-60 adapter)
Ordering Information
ORDERING NUMBER | CONTROL POWER |
SE-704-0U | 120/240 VAC/VDC |
SE-704-0D | 12/24 VDC |
SE-704-0T | 48 VDC |
SE-704-03 | 24 VAC |
ACCESSORIES | REQUIREMENTS |
SE-CS30 Series | Required |
PGA-0500 | Optional |
PMA-55, PMA-60 | Optional |
Accessories
SE-CS30 Series Ground-Fault Transformer
Required zero-sequence current transformer specifically designed for low level detection. Flux conditioner is included to prevent saturation.
PGA-0500 Analog % Current Meter
Optional panel-mounted analog meter displays ground fault current as a percentage of the set-point or 5 A.