The MP8000 is an advanced motor protection electronic overload relay that is fully programmable via Bluetooth using the Littelfuse app on an Android or iPhone mobile device. It is easy to use and arc-flash safety is increased because the app allows settings to be modified and real-time operational information viewed. Viewing operational information and faults on the app does not require the user to open the control panel.
The MP8000 protects any motor drawing 0.5-1,000 full load Amps (external CTs are required above 100 amperes). It is designed for single or 3-phase systems with operating voltages of 90-690 VAC (use of external potential transformers can extend upper voltage range above 690 VAC). Common applications include conveyor systems, HVAC equipment, saws and grinders, fan motors, and almost any pumping application.
Protection is unsurpassed by combining overload, voltage, phase loss and reversal, voltage and current unbalance, power monitoring, and underload in one package. For standalone applications, the Bluetooth interface can be used when paired with a smartphone or tablet. The units also feature an Ethernet communications port that can be used to form an Ethernet Modbus TCP/IP network or Ethernet/IP. Units can be remotely monitored and controlled from a PC, or SCADA system, and data logging through a PC with the optional Solutions software or other software program using the MP8000 memory map. This capability allows for a simple cost-effective way to further enhance arc-flash safety.
Features & Benefits
Bluetooth interface
Visual indication for programming, viewing real-time voltage or current, and last fault information (date and time stamped)Programmable voltage and current setting
Allows usage on wide range of systems3 selectable restart options
Choose from automatic, semi-automatic, or manual to best meet individual application needs4 programmable delay timers
Program separate delay times for power up, rapid cycle protection, motor cool down, and underload restartingFlexible reset
Reset can be done through pushbutton on panel, remotely via the networkNetwork communications capability
Compatible with Ethernet Modbus TCP/IP and Ethernet/IP
Advanced Features
- Overload/Overpower (49)
- Underload/Underpower (37P)
- Overcurrent (51)/Jam
- Undercurrent (37)
- Current Unbalance/Phase Loss (46)
- Phase Reversal (47)
- Overvoltage (59)
- Undervoltage (27)
- Voltage Unbalance (47)
- Rapid Cycling/Jog
- Contactor Failure
- Zero-Sequence Ground Fault (50Ns)
- PTC Motor Overtemperature (49)
Specifications
Functional Characteristics
- Frequency: 50/60Hz
- TC- Overcurrent Trip Class: Trip class 02-60 or linear
Output Characteristics
Output Contact Rating
- Control relay: SPST - Form A
- Auxiliary relay: SPDT - Form C
- Pilot Duty Rating: B300
- General Purpose: 5A @ 240VAC
General Characteristics
Ambient Temperature Range
- Operating: -40° to 70°C (-40° to 158°F)
- Storage: -40° to 85°C (-40° to 185°F)
Accuracy
- Voltage: ±1% of reading ±0.5 V
- Current: ±2% (2 to 100 amperes direct)
- Timing: +/-0.5% of setting +/- 1second
- GF Current: ±5%
Repeatability
- Voltage: ±0.5%
- Current: ±1% (2 to 100 A direct)
- Power Consumption: <5 W
- Pollution Degree: 3 (conformal coating standard)
- Class of Protection: IP20
- Relative Humidity: 10-95%, non-condensing per IEC 68-2-3
- Terminal Torque (depluggable terminal blocks): 5.5 in.-lbs.
- Terminal Torque (Earth Ground): 7.9 in.-lbs.
Standards Passed
- Electrostatic Discharge (ESD): IEC 61000-4-2, Level 3, 6kV contact, 8kV air
- Radio Frequency Immunity (RFI), Conducted: IEC 61000-4-6, Level 3 10V/m
- Radio Frequency Immunity (RFI), Radiated: IEC 61000-4-3, Level 3 10V/m
- Fast Transient Burst: IEC 61000-4-4, Level 3, 3.5kV input power
- Surge: IEC 61000-4-5, Level 3, 2kV line-to-line; Level 4, 4kV line-to-ground
- FCC Rating: Part 15.107 for emissions, Part 15.247 for intentional radiators
- Short Circuit Withstand Rating: 100kA symmetrical at 690VAC
- Hi-Potential Test: Meets UL508 (2 x rated V +1000V for 1 minute)
Safety Marks
- cULus: UL60947, UL1053, C22.2 (File #E68520)
- CE: IEC 60947 Edition 5.2, IEC 60947-8
- Maximum Conductor Size (with insulation): 0.63”
- Dimensions: H 74.42 mm (2.93”); W 103.63 mm (4.08”); D 121.67 mm (4.79”)
- Weight: 0.85 lbs (13.6 oz, 385.6 g)
- Mounting Method: Surface mount (4 - #8 screws) or DIN-rail mount
Ordering Information
MODEL | LINE VOLTAGE | MOTOR FULL AMP RANGE | DESCRIPTION |
MP8000 | 90-690VAC (use of external potential transformers can extend upper voltage range above 690VAC) | 0.5-1,000A+ (external CTs required above 100A) | Provides remote wired communication via Ethernet Modbus TCP/IP or Ethernet/IP |
Accessories
ZSCT Series Current Transformer
Used with Littelfuse relays to detect low levels of earth-leakage current.
VIDEO
Top FAQs
The MP8000 has a wide voltage and current range and operates on 50/60 Hz to protect any motor or pump.
It can also be used to retrofit older current-only based electronic overloads.
It can operate between 90-690VAC and 0.5-1,000A.
-40oC to 70oC
Traditional relays require the user to open the electrical cabinets (where relays are typically installed) panel door to use the relay, whether it’s to modify the settings, or to review the cause of a trip event.
Opening the panel door exposes the worker to shock hazards. Bluetooth, however, enables remote access to these settings, metering and data log information which prevents personnel from unnecessarily having to open the door, thus less exposure to risks.
- Overload (Overpower) (49)
- Underload (Underpower) (37P)
- Overcurrent (51)/Jam
- Undercurrent (37)
- Current Unbalance/Phase Loss (46)
- Phase Reversal (47)
- Overvoltage (59)
- Undervoltage (27)
- Voltage Unbalance (47)
- Rapid Cycling/Jog
- Contactor Failure
- Zero-Sequence Ground Fault (50Ns)
- PTC Motor Overtemperature (49)
The MP8000 can be used in both single phase and 3 phase applications.
Yes, the MP8000 can be put into current-only mode which will disable voltage-based protection functions. However, Littelfuse strongly recommends utilizing the voltage-based protection functions for superior protection especially prior to motor startup.
The current-only mode is intended for retrofit applications on voltages above 690 VAC.
The MP8000 can be surface or panel mounted, or installed on a DIN rail.
No, the MP8000 uses Bluetooth to connect to your smart phone or tablet via the Littelfuse app, This enhances the users safety as it allows remote access.
Yes, you can access the information remotely through the Littelfuse MP8000 PC software or through other software programs communicating with the MP8000 through the Ethernet interface. Contact Fuseco for information on how to download this software.
We're here to help
Talk to an expert today.
Our friendly team of highly trained specialists will quickly assist you.
We promise to respond within 4 business hours (AEST).
Or you will receive $100 off your next purchase. Read how it works.
Applicable Industries
Protection Relays

Hi Tim, just wanted to thank you and the Fuseco team for your help. You've managed to help us solve some nagging issues here and the Littelfuse SE-330AU relay installation has saved us a lot of time. Thanks!
Mark Sherman
PGS Silver, Queensland

Just wanted to send a note of thanks to you guys. When it comes to relays, your advice & service is high level & appreciated. Cheers.
Jesse Marshall
Newcrest WA

The Littelfuse SE-701 & the CT's are functioning well. Thanks guys, really appreciate your help. Good to work with people you can rely on.
Cliff Peligro
Alpha Coal, Queensland
Technical Support
Our experts are all pre-eminent leaders in electrical products who provide excellent support in their areas of expertise.
Technical supportTalk to an expert
Our friendly team are highly trained product experts who really enjoy helping customers find what they need.
call 1300 387 326Enquire by email
We promise to respond within 4 business hours (AEST) or you will receive $100 off your next purchase.
Enquire now